Boiler fault codes

Bosch boiler faults: fault codes, causes and parts (page 2 of 3)

Codes 151 to 300 of the 377 fault codes for Bosch. Looking for a specific code? Use the search on the first page.

Bosch boiler fault codes 151 to 300 of 377

The code list is split over 3 pages. Looking for a specific code? Use the search on the first page: it searches all 377 codes in one go.

CodeCause
B2U565The difference between flow and return temperature is too large > 60K.
B2U565The difference between flow and return temperature is too large >60K.
B5L542Incomplete communication with the burner control unit
B5L542Incomplete communication with the burner control unit.
B5L543No communication with the burner control unit
B5L543No communication with the burner control unit.
B6A577No flame within the safety time
B6L514Flame interruption within the flame stabilisation time.
B6L515Loss of the ionisation signal during operation.
B6L515Loss of the ionisation signal during operation
B7A550Undervoltage
B7A551Power interruption
B7P549The safety circuit is open
B8L579No gas supply pressure
B8U584Changeover module no feedback
C1Pressure switch open during operation.
C1Fan speed too low. .
C1Fan speed too low.
C1Pressure switch is open during operation.
C1264The control signal or the voltage of the fan has been lost during operation.
C4Pressure switch does not open during standstill periods.
C4Pressure switch does not open in the idle state.
C4273The boiler has been switched off for a maximum of 2 minutes because the boiler has been in continuous operation for 24 hours. This is a safety check.
C6Pressure switch does not close.
C6Fan does not run.
C6Pressure switch does not close.
C6215The fan is running too fast.
C6216The fan is running too slowly.
C7214Fan does not run during the start-up phase [0/c/\|.
C7217The fan runs irregularly during start-up.
CATurbine defective.
CAFlow meter (turbine) defective.
CCOutdoor temperature NTC not recognised.
CCOutdoor sensor of a TA 211 E has an open circuit.
CCOutdoor temperature sensor not recognised.
CCOutdoor sensor of a TA 211 E has an open circuit
CCOutdoor temperature sensor not recognised.
CE207The heating water pressure is too low, lower than 0.8 bar.
CE267After four attempts the pressure sensor has been unable to measure sufficient pressure rise (water flow) on the heating side. This check is repeated approx. every 5 min until sufficient pressure rise on the heating side is measured.
CE329The pressure sensor measures insufficient pressure rise (water flow).
CF288The water pressure is too high (> 5.7 bar) or the contacts of the pressure sensor are open-circuit.
CF289The contacts of the pressure sensor are short-circuited.
CF350The contacts of the flow temperature sensor are short-circuited.
CF351The contacts of the flow temperature sensor are open-circuit.
D1LSM in lockout.
D3Jumper 8-9 not recognised.
E0Internal error.
E0Module error.
E0Internal error on PCB.
E2Flow NTC has an open circuit or short circuit.
E2Flow NTC defective.
E2Flow NTC fault
E2Flow temperature sensor defective.
E2222The contacts of the flow temperature sensor are short-circuited.
E2223The contacts of the flow temperature sensor are open-circuit.
E3347The return temperature sensor has measured a higher central heating water temperature than the flow temperature sensor. A restart follows after 10 minutes.
E5The flow temperature is > 100°C.
E5Burner temperature sensor temperature exceeded.
E7Burner temperature sensor is open-circuit or short-circuited
E7Burner temperature sensor is open-circuit or short-circuited.
E9Safety temperature limiter has been activated.
E9Temperature limiter in the heat exchanger or flue gas temperature limiter has switched off.
E9The maximum protection of the heat exchanger is activated when the temperature rises above 105°C.
E9Temperature limiter in flow has been activated.
E9Heat exchanger maximum thermostat or flue gas maximum thermostat has tripped.
E9Temperature limiter in flow has switched off.
E9224The maximum or burner thermostat has measured too high a temperature and is open.
E9276The flow temperature sensor has measured a temperature higher than 95 °C.
E9285The return temperature sensor has measured a temperature higher than 95°C.
E9316The flue gas sensor has measured too high a temperature.
E9318The contacts of the flue gas sensor are open-circuit.
EAFlame not detected (no ionisation).
EAThe burner does not ignite.
EAFlame not detected.
EANo ionisation current.
EA227Insufficient ionisation current has been measured after the burner ignited.
EA229Insufficient ionisation current has been measured during burning.
EA234The contacts of the gas valve are open-circuit.
EA261The burner control unit is defective.
EC256The burner control unit or the KIM is defective.
EC346The temperature of the flue gas sensor rises too quickly.
EE348During hot water mode: the flow temperature is higher than 85 °C.
EF345The flow temperature sensor measures no temperature rise after a burner start.
EF349The temperature difference measured at low load between the flow temperature sensor and the return temperature sensor is too large.
EH258The burner control unit or the KIM is defective.
Ed343During heating mode: the temperature of the flue gas sensor rises, but the temperature of the flow temperature sensor does not.
Ed344During hot water mode: the temperature of the flue gas sensor rises, but the temperature of the flow temperature sensor does not.
F0Internal error.
F0Internal fault.
F0237The burner control unit or the KIM is defective.
F0238The burner control unit or the KIM is defective.
F0239The burner control unit or the KIM is defective.
F0246The burner control unit or the KIM is defective.
F0250The burner control unit or the KIM is defective.
F0251The burner control unit or the KIM is defective.
F0252The burner control unit or the KIM is defective.
F0253The burner control unit or the KIM is defective.
F0254The burner control unit or the KIM is defective.
F0259The burner control unit or the KIM is defective.
F0262The burner control unit or the KIM is defective.
F0263The burner control unit or the KIM is defective.
F0272The burner control unit or the KIM is defective.
F0279The burner control unit or the KIM is defective.
F0280The burner control unit or the KIM is defective.
F0290The burner control unit or the KIM is defective.
F1Internal data error.
F1Internal data error.
F7Flame is detected although the boiler is switched off.
F7Incorrect ionisation signal.
F7Flame is detected although the appliance is switched off.
F7Flame is detected although the boiler is switched off.
F7228An ionisation current was measured before the burner started.
F7306An ionisation current was measured after the burner was extinguished.
F7328There has been a brief interruption of the mains voltage.
F9Defect in the electrical circuit of the gas valve.
FAFlame is detected after gas shut-off.
FAAfter gas shut-off: flame is detected.
FAIonisation current persists after control shut-off.
FdThe reset button was pressed by mistake.
FdThe reset button was pressed by mistake.
FdReset button was pressed accidentally.
FdThe reset button was pressed although the reset button was not illuminated.
Fd231The mains voltage was interrupted during a lockout fault.
H031013Operating hours elapsed
H061016Frequent flame interruptions
H07The measured heating water pressure is too low. The output for both heating mode and hot water mode is limited.
H071017Water pressure too low
H081018Service time elapsed
I--ICalibration of the NTC sensor (see manual page 33).
OAAppliance in switching optimisation programme
OA-Appliance in switching optimisation programme
OCStart of burner start
OC-Start of burner start
OEThe appliance is in standby, heat demand is present but too much energy is being supplied.
OE-The appliance is in standby, heat demand is present but too much energy is being supplied.
OFInsufficient flow through the boiler
OF-Insufficient flow through the boiler
OHThe appliance is in standby, no heat demand present.
OH-The appliance is in standby, no heat demand present.
OLOpening of the gas valve
OL-Opening of the gas valve
OPWaiting for fan to start
OP-Waiting for fan to start
OUStart of the burner start programme
OU-Start of the burner start programme.
OYThe actual heating water temperature is higher than the desired boiler water temperature.
OY-The actual heating water temperature is higher than the desired boiler water temperature.
P1, P2, P3, P1..Please wait, initialisation.
P1, P2, P3, P1…Initialisation has not taken place. .
P1, P2, P3, P1…Please wait, initialisation.

Bosch parts are available from Instalpunt. Back to the first page with the most searched codes and frequently asked questions.