Part of the guide Troubleshooting a boiler fault
Short answer: if the boiler reports water pressure that is too low or too high while the pressure gauge shows a normal 1.5 to 2 bar, the water pressure sensor or its wiring is the suspect, not the system. Codes such as Remeha E.00.40, Nefit 1065, Vaillant F.73 and F.74 or AWB F 9 say exactly that: sensor open circuit, short circuit or out of range. A new sensor costs € 21 to € 54. If the pressure really is dropping, the problem is the expansion vessel or a leak, and you should read Water pressure keeps dropping. Below you can see how to tell the two apart and which sensor fits which appliance.
Sensor or switch?
Older boilers have a water pressure switch: a diaphragm with a contact that closes as soon as the pressure rises above about 0.5 to 0.8 bar. The boiler then only knows "enough pressure" or "too little pressure". Modern boilers have an electronic pressure sensor that measures the pressure continuously, usually 0 to 4 bar converted into a voltage of 0.5 to 3.5 volts. This lets the boiler show the pressure on the display, warn before it blocks and, with some brands, even top up automatically. Both are located on the hydro block or on the return pipe inside the boiler.
How to recognise a faulty sensor
| What you see | Likely | What to do |
|---|---|---|
| Display shows 0.0 or an impossible value, pressure gauge reads 1.5 bar | Sensor or plug | Replace the sensor, check the wiring |
| Code "sensor open/short-circuit/out of range" | Sensor, cable or connector | See codes below |
| Code "pressure too low", display and gauge both low | Genuine pressure loss | Topping up, find the cause |
| Pressure high when hot and low when cold | Expansion vessel | Water pressure keeps dropping |
| Message comes and goes with vibrations or after the pump starts | Loose connector, break in the cable | Have the plug and cable checked |
| Pressure is fine but the boiler will not top up automatically | Sensor reads too high | Replace the sensor |
A simple check you can do yourself: if the boiler has a display showing the pressure as well as a separate pressure gauge, compare the two. A difference of more than 0.3 bar points to the sensor. Top up a little and see whether the display follows; if the value stays the same, the sensor is not measuring.
The codes per brand
| Brand | Sensor fault | Genuine pressure warning |
|---|---|---|
| Remeha | E.00.40 open/below range, E.00.41 short-circuit/above range, A.00.42 sensor not detected | A.02.06 pressure below minimum |
| Nefit Bosch | 1065 sensor faulty or not connected | 207 / 2E 207 pressure too low, 1017 |
| Vaillant | F.73 open circuit, F.74 short circuit, F.09 sensor or wiring | F.21 too low, F.22 too high |
| Bosch | 1065 W | CE207, 1017 W |
| AWB | F 9 sensor broken or wiring, F.73, F.74 | 21 too low, 22 too high |
| ATAG | 102 sensor error, C 78 out of range or not connected, Bx12sc01 open, Bx12sc02 short-circuited | 118 too low, 117 too high |
Note the distinction the manufacturers themselves make. Remeha A.02.06 is a warning about the actual pressure, E.00.40 is about the sensor. With Nefit, 207 relates to the pressure and 1065 to the sensor. So do not order a sensor for every pressure message.
Why sensors fail
The sensor sits in the heating water. Sludge and magnetite settle in the small channel to the diaphragm, making it slow or inaccurate; that is why a dirty system produces sensor faults more often. Moisture also gets into the connector, especially on boilers where a siphon or a leaking coupling sits above the sensor. And with the small plug-in connectors, the contact can work loose through vibration. An engineer will therefore first check the plug and cable and measure the voltage before replacing the sensor.
Replacing it: what can you do yourself?
The sensor is a water-side part: no gas or flue gas is involved. Even so, on almost all boilers it is behind the casing, and opening and refitting the casing of a gas appliance is a job for a certified gas engineer. Our rule is therefore: have it done, but have the right part ready so it can be done in one visit. The work itself is quick: depressurise the boiler, release the retaining clip or union nut, remove the sensor, fit the new one with a new O-ring, refill, vent and check the reading. On Intergas the sensor is held with a clip and a retaining spring; order the spring at the same time.
Which sensor fits which appliance?
The sensors and switches below come from our catalogue; prices include VAT. Always check the appliance type; some brands have a screw-in and a clip-in version side by side.
| Brand | Part | Article number | Price |
|---|---|---|---|
| Intergas | Heating pressure sensor, clip, service set | 8063340 | € 31.95 |
| Intergas | Service set pressure sensor, screw-in | 8069577 | € 53.95 |
| Intergas | Pressure sensor retaining spring | 8063321 | € 6.95 |
| Remeha | Pressure switch Avanta | 8010259 | € 27.95 |
| Remeha | Pressure sensor (Calenta, Tzerra) | 8012610 | € 36.95 |
| Remeha | Water pressure sensor | 8010261 | € 48.95 |
| Nefit Bosch | Pressure sensor | 8029754 | € 33.95 |
| Nefit Bosch | Pressure sensor ProLine NxT | 8029513 | € 31.95 |
| Nefit Bosch | Electronic pressure sensor with screw thread | 8029080 | € 45.95 |
| Vaillant | Pressure sensor VHR 18-22/3C, 24-28/3C | 8058957 | € 20.95 |
| Vaillant | Pressure sensor (ecoTEC) | 80501434 | € 45.95 |
| Bosch | Pressure sensor 6 bar | 80200504 | €38.95 |
| AWB | Water pressure sensor | 8077371 | €35.95 |
| AWB | Pressure sensor ThermoMaster | 8070762 | € 32.95 |
| ATAG | Pressure sensor water trap | 8137098 | € 34.95 |
| Itho Daalderop | CH water-side pressure sensor (also heat pump) | 8170009 | € 37.95 |
| Ferroli | Low water pressure protection Mega/Dens/Star | 8113229 | €38.95 |
All pressure sensors and switches are listed under pressure switches. If you cannot find your appliance, send us a photo of the rating plate and of the old sensor showing the printed number; we will look up the correct part.
Frequently asked questions
Can I use the boiler with a faulty pressure sensor?
Usually not: the boiler blocks because without a pressure reading it does not know whether there is water in it. Resetting helps only temporarily at best. If the pressure gauge reads correctly, there is no danger, but the boiler will stay off until the sensor has been replaced.
How does an engineer test the sensor?
With a multimeter: a supply voltage of 5 volts at the connector and an output voltage that follows the pressure, usually around 1.5 to 2 volts at 1.5 bar. No output voltage or a fixed value means a faulty sensor; no supply points to the cable or PCB.
Is a pressure sensor universal?
The measuring technology is the same for many brands (Huba Control), but the connection, the plug and the measuring ranges differ. So use the part for your appliance type; the wrong sensor gives an incorrect pressure reading and therefore new faults.
Why does my boiler only show a pressure sensor fault when starting up?
When the pump starts, the pressure changes briefly and the appliance vibrates. A connector that is only just making contact loses it at that moment. Have the plug checked and replace the cable if necessary; the sensor itself is often still fine.
Also in this guide
- Topping up your boiler: step-by-step plan, correct pressure and tips per brand
- Does an Intergas boiler have a three-way valve? No, and this is what it has instead
- Original or alternative boiler part: where it is safe, where it is not, and what it means for your warranty
- Automatic air vent on a boiler or underfloor heating: how it works, when it is faulty, cap open or closed, and which one fits
- Back to the overview: Troubleshooting boiler faults